How Long Will a 200Ah Battery Last? The Arithmetic, Honestly Done
· 9 min read · Energy Links Ghana
The short version. One 12V 200Ah lead-acid battery holds about 2.4 kilowatt-hours on paper. You can safely use roughly half of that, and the inverter loses a little of what is left, so plan on somewhere near 1 kilowatt-hour of real delivered energy per battery per cycle. Divide that by your load in watts and you have your hours.
- A 300W load — a few lights, a fan, a TV, a router — runs for roughly three hours
- A 500W load runs for roughly two hours
- A 1000W load runs for roughly one hour
The important version. Those numbers get worse as the load gets heavier, and they get worse again if the battery is warm or old. And in Ghana there is a second question nobody asks at the point of sale, which matters just as much: can you put that kilowatt-hour back in before the next outage?
This post does the arithmetic properly, using figures from manufacturers' own documentation rather than rules of thumb.
Step 1: what 200Ah actually means
Amp-hours are not energy. Watt-hours are energy, and you get them by multiplying amp-hours by the battery voltage.
- A 12V 200Ah battery: 12 multiplied by 200, which is 2,400 watt-hours, or 2.4 kWh
- Two of those in series, making 24V 200Ah: 4,800 watt-hours
- Four in series, making 48V 200Ah: 9,600 watt-hours
Note what happened there. Four 200Ah batteries at 48V hold four times the energy of one at 12V, even though the bank is still "200Ah". This is why the Ah figure on its own tells you very little, and why a quotation that specifies only "200Ah" has not told you what you are buying. Higher system voltage also means lower current for the same power, which means thinner cable losses and less heat. For anything above a very small system, 24V or 48V is the better engineering.
Step 2: subtract the part you must not use
A lead-acid battery that is routinely emptied does not last. Every manufacturer publishes a cycle-life curve showing the same thing: the shallower the discharge, the more cycles you get.
The Canbat deep-cycle datasheet we reference below, for instance, includes a chart titled "Cycle Life Relation to Depth of Discharge" plotting separate curves for 100 percent, 50 percent and 30 percent depth of discharge. Every serious sealed-battery datasheet has the equivalent.
What we are not going to do is give you a cycle number. The published figures for lead-acid cycle life at 50 percent depth of discharge vary enormously between sources and between constructions — flooded tubular, AGM and gel are not the same battery and are not rated the same way. Anyone quoting you a single confident number across all of them is guessing.
What to demand instead: the cycle-life curve from the datasheet of the specific battery you are being offered, at a stated depth of discharge and a stated temperature. If the supplier cannot produce it, you are buying a promise rather than a specification.
For planning purposes, the conventional working figure for lead-acid is 50 percent. So of 2,400 watt-hours, treat about 1,200 as yours to use. Lithium permits a deeper discharge — which chemistry suits which job is covered in which battery for your inverter.
Step 3: subtract the inverter's losses
The inverter converts DC to AC and takes a cut. A good one is somewhere in the high eighties to low nineties as a percentage at a sensible load. Call it 88 percent.
So: 1,200 watt-hours usable, multiplied by 0.88, gives about 1,055 watt-hours delivered to your sockets.
That is the number to divide by your load. One 12V 200Ah lead-acid battery gives you, in round terms, one kilowatt-hour of real work.
Step 4: the correction almost nobody applies — discharge rate
Here is where the published numbers stop matching the sales pitch, and the evidence is unambiguous.
A battery's amp-hour rating is quoted at a slow discharge. Empty it faster and it simply gives you less.
Take a real datasheet. The Canbat CDC50-12 deep-cycle sealed lead-acid battery is rated and published at these discharge characteristics, all at 25 degrees Celsius:
- At the 20-hour rate: 53.6Ah, drawing 2.68A
- At the 1-hour rate: 32.3Ah, drawing 32.3A
Same battery. Same charge. Forty percent less capacity, purely because it was discharged in an hour instead of twenty.
Victron Energy's battery-monitor documentation describes the same effect with its own worked example. A battery rated 100Ah at C20 — 5A for twenty hours — gives about 75Ah if discharged in five hours, and Victron states it "may only give C2 = 56Ah" when fully discharged in two hours. Victron's monitors default to a Peukert exponent of 1.25 for lead-acid, on an adjustable range of 1.00 to 1.50, where 1.00 would be a perfect battery that lost nothing to rate.
So what does this do to your 200Ah battery?
- A light load that empties the bank over eight or ten hours sees something close to the rated capacity
- A heavy load that empties it in an hour sees substantially less — the Canbat figures suggest a loss on the order of 40 percent at the one-hour rate
This is the single reason the biggest discrepancy between promise and delivery happens on heavy loads. An inverter running a fridge, a few lights and a fan all evening is being kind to the battery. The same bank asked to run a pressing iron is not getting the capacity on the label.
Step 5: the question nobody asks — can you refill it?
This is the Ghanaian half of the problem, and it is routinely ignored.
Having taken 1,200 watt-hours out, you must put rather more than that back, because charging is not free either. At a 20A charge current on a 12V bank, you are putting in roughly 240 watts. Even ignoring the inefficiency, refilling 1,200 watt-hours takes more than five hours of good charging, and the last portion of a lead-acid charge is deliberately slow, so in practice it is longer.
Now put that against what the mains actually does here. The Kleinman Center study of voltage quality in Accra measured customers averaging about 219V against a 230V nominal, with voltage more than 20 percent below nominal common during the 6pm to 10pm peak, and about 1.6 hours of bad voltage per day. The regulator's 2005 rule requires sustained voltages within 10 percent of nominal.
A charger designed around a stable 230V input charges slowly or incompletely at 200V. So the sequence that actually happens is this: the bank discharges in the evening, the mains comes back marginal, the charger never finishes the job, and the next outage starts from a bank that is perhaps 70 percent full. The owner concludes the battery is faulty. Usually it is not. The mechanism is set out in what is normal voltage in Ghana and in why a UPS or inverter will not charge.
This is also the strongest practical argument for solar charging on a hybrid system: the panels refill the bank during the day, when the grid's problems are irrelevant. See hybrid or off-grid.
Step 6: heat, which is not optional here
Every figure above is quoted at 25 degrees Celsius. The Canbat sheet states a nominal operating temperature of 25 degrees, and Riello UPS's white paper on battery lifespan puts the optimum band for sealed lead-acid at 20 to 25 degrees Celsius, and calls high ambient temperature "the most common cause of premature battery failure."
An enclosed cupboard in Accra is not 25 degrees. Batteries belong somewhere ventilated and shaded, off the floor, with air able to move between them. This costs nothing at installation and is the cheapest extra year you will ever buy.
Putting it together: three honest answers
One 12V 200Ah lead-acid battery. About 1 kWh delivered. Lights, fans, a TV, a router, phone charging: an evening. A fridge as well: expect noticeably less, because the compressor's starting surge and cycling are hard on the bank.
Two 200Ah batteries at 24V. About 2 kWh delivered. A realistic small-household backup for a long evening outage, provided the loads are chosen rather than assumed.
Four 200Ah batteries at 48V. About 4 kWh delivered. Now you are into real whole-house territory, and the charger and inverter must be matched to it.
Beyond that, the sizing question is better approached from the load end than the battery end. Our inverter sizing guide works through the running watts and surge watts that set the inverter rating, and the daily kilowatt-hours that set the bank.
Frequently asked questions
How long will a 200Ah battery last with a 1000W inverter?
The inverter rating is not the load. A 1000W inverter running a 300W load behaves like a 300W draw, and that is what sets the hours. If you genuinely draw a full 1000W, expect around an hour from one 12V 200Ah lead-acid battery, and rather less than the arithmetic suggests because of the discharge-rate loss above.
How long will a 200Ah battery run a refrigerator?
A domestic fridge averages far less than its nameplate because the compressor cycles. But it starts repeatedly, and starting surges are the part batteries dislike. One 200Ah battery will typically carry a modest fridge for an evening and not much else. Size for the fridge plus whatever else you actually intend to run.
Is a 200Ah lithium battery better than a 200Ah lead-acid one?
It delivers more usable energy from the same nameplate figure, because it tolerates a deeper discharge and loses less capacity at higher discharge rates. Whether that is the right purchase depends on the application and on datasheet figures rather than claims — see which battery for your inverter.
Can I just add more batteries later?
Only with care. Mixing new batteries with used ones in the same bank drags the new ones down to the condition of the old. Plan the bank voltage and size at the start, and make sure the charger can refill whatever you install.
Does this apply to my UPS as well?
The principle does, but the numbers do not — a UPS discharges a small sealed pack in minutes at a very high rate, which is a harsher case than anything on this page. That calculation is in how to calculate UPS backup time.
Get the bank sized against your real load
The arithmetic on this page is honest, and it is still only a first pass. The real answer depends on your actual load profile, the specific battery's datasheet, the temperature where the bank will live, and whether your supply can recharge it between outages.
Our engineers will measure the load, measure what your mains actually does across a working day, ask for the datasheet rather than guessing at it, and specify a bank that will still be delivering in year three.
Contact us for a survey, or see the inverters, batteries and power equipment we stock.